Mounting the Device to a Panel

For panel installations, the RUGGEDCOM RX1510 can be equipped with panel/DIN rail adapters pre-installed on
each side of the chassis. The adapters allow the device to be attached to a panel using screws.
To mount the device to a panel, do the following:
1.
Place the device against the panel and mark the mounting holes on the panel.
Figure 3: Panel Mounting
1. Screw    2. Panel/DIN Rail Adapter
2.
Prepare the mounting holes
3.
Align the device with the mounting holes and secure it to the panel.
Section 2.5

Connecting the Failsafe Alarm Relay

The failsafe relay can be configured to latch based on alarm conditions. The NO (Normally Open) contact is closed
when the unit is powered and there are no active alarms. If the device is not powered or if an active alarm is
configured, the relay opens the NO contact and closes the NC (Normally Closed) contact.
NOTE
Control of the failsafe relay output is configurable through ROX II. One common application for this
relay is to signal an alarm if a power failure occurs. For more information, refer to the ROX II User
Guide for the RUGGEDCOM RX1510.