Parameterization - Siemens SIMATIC S7 Manual

S7 open modbus / tcp communication via the integrated pn interface of the plc
Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

Error messages of FB MODBUSPN at the output STATUS_MODBUS
STATUS
Event text
(Hex)
A035
The parameterized areas data_type_3 and data_type_5
overlap.
A036
The parameterized areas data_type_3 and data_type_6
overlap.
A037
The parameterized areas data_type_3 and
data_type_7overlap.
A038
The parameterized areas data_type_3 and
data_type_8overlap.
A045
The parameterized areas data_type_4 and data_type_5
overlap.
A046
The parameterized areas data_type_4 and data_type_6
overlap.
A047
The parameterized areas data_type_4 and data_type_7
overlap.
A048
The parameterized areas data_type_4 and data_type_8
overlap.
A056
The parameterized areas data_type_5 and data_type_6
overlap.
A057
The parameterized areas data_type_5 and data_type_7
overlap.
A058
The parameterized areas data_type_5 and data_type_8
overlap.
A067
The parameterized areas data_type_6 and data_type_7
overlap.
A068
The parameterized areas data_type_6 and data_type_8
overlap.
A078
The parameterized areas data_type_7 and data_type_8
overlap.
A079
The connection ID of parameter ID is not defined in DB
MODBUS_PARAM.
A07A
An invalid value ID is parameterized. Range of values is
1 to 4095.
A07B
The parameter ID exists twice in the parameter DB.
A07C
An invalid value data_type_x was given. The value range
is 0 to 4.
A07D
Parameter data_type_1 is not defined. The parameter
area _1 is the default area and must be defined.
A07E
The DB number of db_x is identical to the number of the
parameter DB MODBUS_PARAM or to the instance DB.
A07F
The data block defined at DB_PARAM is no parameter
DB for Modbus communication. The length information in
DBW0 was changed or a wrong DB was defined.
A080
The parameter DB_PARAM was changed without a
restart of the CPU.
MODBUS / TCP communication via the integrated PN interface of the CPU
2XV9450-1MB02; Manual edition 2.1
Remedy
Correct the parameterization in
DB MODBUS_PARAM
The data areas must not
contain any overlapping
register areas.
Correct the parameterization at
the input ID.
Correct the parameterization in
DB MODBUS_PARAM.
Correct the parameterization at
the INPUT DB_PARAM.
DB_PARAM is an initialization
parameter. Restart the CPU
after changing this parameter.