Rinnai EX08C Conversion Manual

Rinnai EX08C Conversion Manual

Rhfe-202fta;rhfe-265fta energysaver gas direct vent wall furnace
Table of Contents

Advertisement

Available languages

Available languages

for the conversion from
Natural Gas (NG) to Liquid Propane Gas (LPG)
for the conversion from
Liquid Propane Gas (LPG) to Natural Gas (NG)
for adjustments at high altitude
(greater than 2000 ft / 610 m)
WARNING
This conversion kit shall be installed by a qualified service agency in
accordance with the manufacturer's instructions and all applicable codes and
requirements of the authority having jurisdiction. If the information in these
instructions is not followed exactly, a fire, explosion or production of carbon
monoxide may result causing property damage, personal injury or loss of life.
The qualified service agency is responsible for the proper installation of this
kit. The installation is not proper and complete until the operation of the
converted appliance is checked as specified in the manufacturer's instructions
supplied with the kit.
Conversion Manual for the
EX08C (RHFE-202FTA)
EX11C (RHFE-265FTA)
Energysaver
Gas Direct Vent Wall Furnace
®
English
Safety Symbols ......................... 2
Technical Data .......................... 2
Conversion Procedure .............. 3
Parts List ................................... 11
Données Techniques ................ 7
Haute Altitude ........................... 7
de Gas ...................................... 9
Liste des Pièces ........................ 11

Advertisement

Table of Contents
loading

Summary of Contents for Rinnai EX08C

  • Page 1: Table Of Contents

    Conversion Manual for the EX08C (RHFE-202FTA) EX11C (RHFE-265FTA) Energysaver ® Gas Direct Vent Wall Furnace English Safety Symbols ......2 Technical Data ......2 High Altitude ......2 Conversion Procedure ....3 Adjust Gas Pressure Settings ... 4 for the conversion from ⇒...
  • Page 2: Safety Symbols

    For high altitude installations in Canada, the conversion shall be carried out by a manufacturer’s authorized representative, in accordance with the requirements of the manufacturer, provincial or territorial authorities having jurisdiction and in accordance with the requirements of CAN/CGA-B149.1 or CAN/CGA-B149 installation codes. Rinnai Corporation EX08C, EX11C Conversion Manual...
  • Page 3: Conversion Procedure

    3. Remove the burner screw from the burner 7. Complete the procedure, Adjust Gas Pressure assembly. Settings. Manifold screw locations Flame view port Electrode and leads Injectors Primary Burner screw Secondary damper damper tab Rinnai Corporation EX08C, EX11C Conversion Manual...
  • Page 4: Adjust Gas Pressure Settings

    * For the EX11C with natural gas: Use A1, A2, A3, or A4 for venting up to 7 feet (2.1 m) with one elbow. Use A5, A6, A7, or A8 for venting exceeding 7 feet (2.1 m) with one elbow. Rinnai Corporation EX08C, EX11C Conversion Manual...
  • Page 5: Normal Operating Sequence

    2. If doing a gas type conversion, place the new conversion plate (label) on the front cover. CAUTION When attaching the front panel, do not clip or pinch any of the electrical wires in order to prevent any electrical shock. Rinnai Corporation EX08C, EX11C Conversion Manual...
  • Page 6: Français

    Le technician agréé est responsible de l’installation de cette trousse. L’installation n’est pas adéquate ni compléte tant que le bon fonctionnement de l’appareil converti n’a pas été vérifié selon les instructions du fabricant fournies avec la trousse. Rinnai Corporation EX08C, EX11C Conversion Manual...
  • Page 7: Sécurité Du Consommateur

    Pour des installations d'altitude élevée au Canada, la conversion doit être effectuée en suivant les conditions requises par les autorités des provinces ayant jurisdiction et conformément aux exigences 1 et 2 du Code d’Installation CAN1-B149. Rinnai Corporation EX08C, EX11C Conversion Manual...
  • Page 8: Procédure De Conversion

    être utilisés. (Tirer l'amortisseur secondaire hors utilisant directement l'étiquette sur le côté.) Se référer aux Les emplacements divers de vis Flamber l'hublot L'électrode et mène Injecteurs Amortisseur primaire Vis de brûleur L'étiquette secondaire d'amortisseur Rinnai Corporation EX08C, EX11C Conversion Manual...
  • Page 9: Ajustage Et Reglage De La Presion De Gas

    * Pour le EX11C au gaz naturel : utilisez A1, A2, A3 ou A4 pour ventilation jusqu'à 7 mètres (2.1 m) avec un coude. utilisez A5, A6, A7 ou A8 pour ventilation supérieure plus 7 mètres (2.1 m) avec un coude. Rinnai Corporation EX08C, EX11C Conversion Manual...
  • Page 10 2. Si vous faites une conversion de type de gaz, placer la nouvelle plaque de conversion (étiquette) sur le capot avant. CAUTION Lorsque vous joignez le panneau avant, ne pas d'élément ou aucun des fils électriques pinch afin d'éviter tout choc électrique. Rinnai Corporation EX08C, EX11C Conversion Manual...
  • Page 11: Parts List

    Part No. (Nom de la Pièce) (Numero de pièce) (Gaz) Quantité Injector (Injecteur) AU129-210-0.90 Primary Damper (Registre Primaire) 308F-209-7 Secondary Damper (Registre Secondaire) φ 2.5 X 10 308F-218-3 Conversion Plate (Plaque de Conversion) CP-72317-26 Rinnai Corporation EX08C, EX11C Conversion Manual...
  • Page 12 RHF265-1092X01(00) Printed in Japan 2011.06 © 2011 Rinnai America Corporation...