Mitsubishi Electric MELSEC iQ-R Series User Manual page 165

Canopen module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Information stored as additional information varies depending on the error type.
The following table lists the error types and error details, as well as whether additional information is available.
Error type
Name
0003H
SDO error
0064H
Unknown command
0F0FH
Invalid device status
B0FFH
Bus OFF
FFFFH
Unauthorized access
in the CIF busy state
The following table details the SDO error additional information.
Address
Description
Un\G1002
Node ID
Un\G1003 to
Error code ( Page 29 SDO abort codes)
Un\G1004
• 1003 (3EBH): Low word of the error code
• 1004 (3ECH): High word of the error code
Un\G1005 to
System area
Un\G1066
• Display current parameter
This process displays the command parameters of the previously executed command in 'Command interface (CIF)'
(Un\G1000 to Un\G1066). The command code is not displayed.
The following is the procedure for executing a command of Display current parameter.
Control by the program
'Command execution request' (Y17)
'Command execution completed' (X17)
Un\G1000
(Command code/
Command execution
'Command interface
result code)
(CIF)' (Un\G1000 to
Un\G1066)
Area other than
Un\G1000
 Set the transmit message in 'Command interface (CIF)' (Un\G1000 to Un\G1066) via the program.
 Turn on 'Command execution request' (Y17) via the program.
 FFFFH (CIF busy) is stored in Un\G1000 while the command is being processed.
 When the command execution is finished, 'Command execution completed' (X17) turns on.
 Then, 0000H (Completed) is stored in Un\G1000.
The receive message is stored in an area other than Un\G1000 of 'Command interface (CIF)' (Un\G1000 to Un\G1066).
Retrieve the receive message via the program to check the command parameters of the previously executed command.
 After the command (Display current parameter) is completed, turn off 'Command execution request' (Y17) via the program. When 'Command execution
request' (Y17) is turned off, 'Command execution completed' (X17) also turns off.
For the current parameter display, the buffer memory areas are assigned as follows.
Address
Description
Transmit message
Un\G1000
Command code
• 0000H: Display current parameter
Un\G1001 to
System area
Un\G1066
Description
An SDO error occurred.
An unknown command was executed.
Cannot execute the command.
Cannot receive a CAN message in the bus off state.
'Command interface (CIF)' (Un\G1000 to Un\G1066) was altered by unauthorized write
access in the CIF busy state.
Ò
Ó
SET
instruction
MOV/TO
instruction
ON
OFF
Execution started
OFF
Ô
Command code
Transmit message
Ö
MOV/FROM
instruction
Õ
ON
Execution
completed
FFFFH
Command execution
result code
(CIF busy)
Receive message
Receive message
Command execution result code
• 0000H: Completed
Command parameters of the previously executed command
Additional
information
Available
Not available
Not available
Not available
Not available
×
RST
instruction
OFF
OFF
APPX
Appendix 2 Buffer Memory