1-3. DRY OPERATION
1-3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to set temperature and room
temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the Table 3.
( Table 3 : Compressor frequency )
30,36LRLB
X zone
39rps
J
zone
Y zone
( Fig.2 : Compressor Control based on Room Temperature )
Room
temperature
X zone
Ts+0.5°C
J zone
Ts-1.5°C
Y zone
( Fig.3 : Indoor Fan Control )
Compressor
ON
OFF
Setting air flow
Lo
S-Lo
OFF
10
Operating frequency
45,54LRLB
44rps
0rps
0rps
Room
temperature
Ts+1.5°C
Ts-0.5°C
Ts : Setting temperature
30
60
360
120
360
01-03
120
10
30
(sec)