C.5

Representation of analog values for thermocouples

The following tables list the decimal and hexadecimal values (codes) of the supported
thermocouples.
Table C- 14
Thermocouple type B
Type B in
Values
°C
dec
hex
> 2070.0
32767
7FFF
2070.0
20700
50DC
:
:
:
1820.1
18201
4719
1820.0
18200
4718
:
:
:
250.0
2500
09C4
249.9
2499
09C3
:
:
:
0.0
0
0
< 0.0
-32768
8000
Table C- 15
Thermocouple type E
Type E in
Values
°C
dec
hex
> 1200.0
32767
7FFF
1200.0
12000
2EE0
:
:
:
1000.1
10001
2711
1000.0
10000
2710
:
:
:
-270.0
-2700
F574
< -270.0
-32768
8000
Analog input module AI 8xU/I/RTD/TC ST (6ES7531-7KF00-0AB0)
Manual, 09/2016, A5E03484864-AD
Type B in
Values
°F
dec
hex
> 3276.6
32767
7FFF
3276.6
32766
7FFE
:
:
:
2786.6
27866
6CDA
2786.5
27865
6CD9
:
:
:
482.0
4820
12D4
481.9
4819
12D3
:
:
:
32.0
320
0140
< 32.0
-32768
8000
Type E in
Values
°F
dec
hex
> 2192.0
32767
7FFF
2192.0
21920
55A0
:
:
:
1832.2
18322
4792
1832.0
18320
4790
:
:
:
-454.0
-4540
EE44
< -454.0
-32768
8000
Representation of analog values
C.5 Representation of analog values for thermocouples
Type B in
Values
K
dec
> 2343.2
32767
2343.2
23432
:
:
2093.3
20933
2093.2
20932
:
:
523.2
5232
523.1
5231
:
:
273.2
2732
< 273.2
32768
Type E in
Values
K
dec
> 1473.2
32767
1473.2
14732
:
:
1273.3
12733
1273.2
12732
:
:
0
0
<0
-32768
Range
hex
7FFF
Overflow
5B88
Overshoot
range
:
51C5
51C4
Rated range
:
1470
1469
Undershoot
range
:
0AAC
8000
Underflow
Range
hex
7FFF
Overflow
398C
Overshoot
range
:
31BD
31BC
Rated range
:
0000
8000
Underflow
71