4.4

Address space

The module can be configured differently in STEP 7; see following table. Depending on the
configuration, additional/different addresses are assigned in the process image of the inputs.
Configuration options of AI 8xU/I/RTD/TC ST
You can configure the module with STEP 7 (TIA Portal) or with a GSD file.
When you configure the module by means of the GSD file, the configurations are available
under different abbreviations/module names.
The following configurations are possible:
Table 4- 4
Configuration options
Configuration
1 x 8-channel without value status
1 x 8-channel with value status
8 x 1-channel without value status
8 x 1-channel with value status
1 x 8-channel with value status for
module-internal shared input with
up to 4 submodules
Value status (Quality Information, QI)
The value status is always activated for the following module names:
● AI 8xU/I/RTD/TC ST QI
● AI 8xU/I/RTD/TC ST S QI
● AI 8xU/I/RTD/TC ST MSI
An additional bit is assigned to each channel for the value status. The value status bit
indicates if the read in digital value is valid. (0 = value is incorrect).
Analog input module AI 8xU/I/RTD/TC ST (6ES7531-7KF00-0AB0)
Manual, 09/2016, A5E03484864-AD
Short designation/
module name in the GSD
file
AI 8xU/I/RTD/TC ST
AI 8xU/I/RTD/TC ST QI
AI 8xU/I/RTD/TC ST S
AI 8xU/I/RTD/TC ST S QI
AI 8xU/I/RTD/TC ST MSI
Parameters/address space
Configuration software, e.g., with STEP 7 (TIA Portal)
Integrated in hardware
catalog STEP 7
(TIA Portal)
V12 or higher
V12 or higher
V13 Update 3 or higher
(PROFINET IO only)
V13 Update 3 or higher
(PROFINET IO only)
V13 Update 3 or higher
(PROFINET IO only)
4.4 Address space
GSD file in
STEP 7 (TIA Portal) V12
or higher or STEP 7 V5.5
SP3 or higher
X
X
X
(PROFINET IO only)
X
(PROFINET IO only)
X
(PROFINET IO only)
31