Three-Phase 200V/400V Class - Mitsubishi Electric FR-E700 Instruction Manual

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Terminal
Type
Terminal Name
Symbol
Relay output
A, B, C
(fault output)
RUN
Inverter running
FU
Frequency detection
Open collector
SE
output common
FM
PU connector
USB connector
Note
Set Pr. 267 and a voltage/current input switch correctly, then input an analog signal in accordance with the setting.
Applying a voltage with voltage/current input switch in "I" position (current input is selected) or a current with switch
in "V" position (voltage input is selected) could cause component damage of the inverter or analog circuit of output
devices.
The inverter will be damaged if power is applied to the inverter output terminals (U, V, W). Never perform such wiring.
indicates that terminal functions can be selected using Pr. 178 to Pr. 184 and Pr. 190 to Pr. 192 (I/O terminal function
selection).
Terminal names and terminal functions are those of the factory set.
When connecting the DC power supply, be sure to connect the plus side of the power supply to terminal P/+ and
minus side to terminal N/-. Opposite polarity will damage the inverter.
2.3.3
Terminal arrangement of the main circuit terminal, power supply and the motor
wiring

Three-phase 200V/400V class

FR-E720-0.1K to 0.75K
N/-
R/L1 S/L2 T/L3
Power supply
FR-E720-5.5K, 7.5K
R/L1 S/L2 T/L3
N/-
Power supply
1 changeover contact output indicates that the inverter fault occurs.
Fault: discontinuity across B-C (continuity across A-C), Normal: continuity across B-C
(discontinuity across A-C) Contact capacity 230VAC 0.3A (power factor = 0.4) 30VDC 0.3A
Switched Low when the inverter output frequency is equal to or
higher than the starting frequency (initial value 0.5Hz).
Switched High during stop or DC injection brake operation.∗
Switched Low when the inverter output frequency is equal to or
higher than the preset detected frequency and High when less
than the preset detected frequency.∗
Common terminal of terminal RUN and FU.
Used to output a selected monitored item (such as Output
frequency) among several monitored items. (Not output during
For meter
inverter reset.) The output signal is proportional to the
magnitude of the corresponding monitoring item.
With the PU connector, RS-485 communication can be established.
· Conforming standard: EIA-485 (RS-485)
· Communication speed: 4800 to 38400bps · Overall extension: 500m
FR Configurator can be operated by connecting the inverter to the personal computer through USB.
· Interface: conforms to USB1.1
· Connector: USB mini B connector (receptacle mini B type)
Jumper
P/+
PR
IM
Motor
P/+ PR
Jumper
IM
Motor
Description
· Transmission format: Multi-drop link
· Transmission Speed: 12Mbps
FR-E720-1.5K to 3.7K
FR-E740-0.4K to 3.7K
N/- P/+
Jumper
R/L1 S/L2 T/L3
PR
Power supply
FR-E740-5.5K, 7.5K
R/L1 S/L2 T/L3
Jumper
N/-
P/+ PR
Power supply
Wiring
Permissible load 24VDC
(Maximum 27VDC) 0.1A
(a voltage drop is 3.4V
maximum when the signal is
on)
∗ Low
is
when
the
open
collector output transistor is
ON (conducts). High is when
the transistor is OFF (does
not conduct).
Permissible load current 1mA
1440 pulses/s at 60Hz
IM
Motor
IM
Motor
11
2