Pentair ETi 400 Installation And User Manual page 37

High efficiency heater
Hide thumbs Also See for ETi 400:
Table of Contents

Advertisement

Available languages

Available languages

CONDENSATION MANAGEMENT
The ETi
400 Heater is a condensing appliance. The flue gases will produce condensate while in operation and
®
must be drained correctly. Note: The condensate pH level is between 3.1 and 4.2, Pentair recommends to
neutralize the condensate to avoid potential damage over time to the drainage system, and to comply with
local water authorities where applicable. To neutralize the condensate, use an optional Condensate Neutralizer Kit
P/N 475612 or similar. The condensate drain must be installed so as to prevent accumulation of condensate. When
a condensate pump is not used, the tubing must continuously slope downward toward the drain with no spiraling.
CAUTION! pH levels of 5.0 and below may harm some floor drains and/or pipes, particularly those that are metal.
Ensure that the drain, drainpipe, and anything that will come in contact with the condensate can withstand the acidity.
Damage caused by failure to install a neutralizer kit or to adequately treat condensate will not be the manufacturer's
responsibility.
WARNING! DO NOT allow the exhaust flue gases to vent through the neutralizer. All condensate drains MUST have
a trap to prevent flue gas leakage. Flue gas leakage can cause personal injury or death from carbon monoxide. Check
with local authorities for regulations regarding discharge of condensate to the drain sewer system.
Condensate Maintenance
Annual condensate assembly inspection: Inspect the inside tubing top for any dirt or particles that could collect and clog
the condensate neutralizer cartridge. DO NOT route the condensate outside tubing through any area that is exposed
to freezing temperatures.
Condensate Neutralizer Cartridge Drain/Tubing Installation
To install the external condensate neutralizer cartridge drain/tubing:
1. Connect the PVC socket adaptors to the neutralizer. DO NOT OVERTIGHTEN.
2. Connect the inside tubing to the inlet of the neutralizer cartridge.
3. Indoor Heater Installation (Figure 29): Mount the neutralizer cartridge on the floor near the side of the heater.
Outdoor Heater Installation (Figure 30): Using the provided brackets, secure the neutralizer cartridge onto the
heater base.
4. Connect the outside tubing to the outlet of the neutralizer cartridge. Be sure the tubing is at its highest point at the
cartridge outlet.
5. Route the outside tubing to a drain or to a pump. Maintain a pitch of ¼ in per foot downward from the cartridge
outlet.
6. Fill the condensate trap with water until flow is established through the neutralizer. Note: Observe the neutralizer
during the heater operation to ensure unrestricted flow.
Inside
tubing to
internal
exhaust
pipe
Figure 29. External Neutralizer Cartridge for indoor heater Installation
Rev. C 4/2017
Optional
Outside tubing
External
Condensate
Connect tube to
Neutralizer Kit
cartridge inlet
P/N 475612
Mounting
brackets
ETi 400 High Efficiency Pool and Spa Heater Installation and User's Guide
Section 2: Installation Instructions
(FOR INDOOR OR OUTDOOR HEATER INSTALLATION)
Figure 30. Internal Neutralizer Cartridge
installed on base of heater for outdoor
heater Installation
Out to drain
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents