Installing The Dc Power Supply In The Switch - Cisco Catalyst 2350 Installation Manual

Hide thumbs Also See for Catalyst 2350:
Table of Contents

Advertisement

Installing a DC-Power Supply
Using a ratcheting torque screwdriver, torque the ground-lug screws to 60 lbf-in (960 ozf-in)
Step 6
(Figure
Step 7
Connect the other end of the grounding wire to an appropriate grounding point at your site or to the rack.
Figure 3-5
1

Installing the DC Power Supply in the Switch

Turn off power at the DC circuits. Locate the circuit breakers for the DC circuits, switch the circuit
Step 1
breakers to the OFF position, and tape the circuit-breaker switches in the OFF position.
Use a number-2 Phillips screwdriver to remove the plastic safety cover from the power supply terminal
Step 2
blocks.
Use a number-1 Phillips screwdriver to remove the DC-input power wires from the power terminals.
Step 3
Use a Phillips screwdriver to loosen the two captive screws at the lower edge of the module that secure
Step 4
it to the switch chassis.
Remove the power-supply module from the power slot by pulling on the extraction handle.
Step 5
Insert the new power supply into the power-supply slot, and gently push it in
Step 6
correctly inserted, the power supply is flush with the switch rear panel.
Catalyst 2350 Switch Hardware Installation Guide
3-6
3-5).
Attaching the Ground Lug and Wire Assembly on Catalyst 2350 Switches
1
Single-ground screw and lug ring.
Used with AC power supply.
Chapter 3
Power Supply and Fan Module Installation
2
2
Dual-ground adaptor and dual-hole lug.
Used with DC power supply.
(Figure
3-6). When
OL18479-01