Below Grade Installation - Majestic Designer Installation And Operating Instructions Manual

Direct vent gas fireplace
Table of Contents

Advertisement

BELOW GRADE INSTALLATIONS
When it is not possible to meet the required vent terminal clearances of 12" above grade
level, a snorkel kit is recommended. It allows installation depth down to 7" (178 mm) below
grade level. The 7" (178 mm) is measured from the center of the horizontal vent pipe as it
penetrates through the wall.
Ensure that sidewall venting clearances are observed. If venting system is installed
below ground, we recommend a window well with adequate and proper drainage to
be installed around the termination area.
If installing a snorkel, a minimum 24" vertical rise is necessary. The maximum horizontal run
with the 24" vertical pipe is 36". This measurement is taken from the collar of the fireplace (or
transition elbow) to the face of the exterior wall. See the Sidewall Venting Graph for extended
horizontal run if the vertical exceeds 24".
1. Establish vent hole through the wall. Page 21, Figure 20
2. Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe.
Install window well (not supplied). Refill hole with 12" of coarse gravel leaving a clearance
of approximately 4" below snorkel. Figure 31
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe coming through the wall.
5. Slide the snorkel into the vent pipes and secure to the wall.
6. Level the soil so as to maintain a 4" clearance below snorkel. Figure 31
If the foundation is recessed, use recess brackets (not supplied) for securing lower portion
of the snorkel. Fasten brackets to wall first, then secure to snorkel with self drilling #8 x 1/2
sheet metal screws. It will be necessary to extend vent pipes out as far as the protruding
wall face. Figure 32
Firestop
24"
Minimum
Figure 31 -

Below Grade Installation

53D0419
Screws
Drain
Foundation Wall
FP2059
FP2059
below grade install
Minimum
4" Clearance
Window Well
Gravel
Figure 32 -
Snorkel Installation, Recessed Foundation
VENT INSTALLATION
• Do not back fill around snorkel.
• A clearance of at least 4" must be
maintained between the snorkel
and the soil.
Foundation
Recess
Watertight Seal
Around Pipe
FP2060
FP2060
snorkel
Snorkel
Wall Screws
Sheet Metal
Screws
5