Engineer Programming Via the Keypad
10.4.9 Mains Sig Delay
10.4.10 Keypad Timeout
10.4.11 Wireless Fail to Set (FTS)*
10.4.12 Wireless Lost*
10.4.13 Engineer Access
58
Siemens Building Technologies
Fire Safety & Security Products
To set the mains sig delay:
1.
Scroll to the MAINS SIG DELAY programming
option.
2.
Press SELECT.
3.
Enter the preferred time (0-60 min).
4.
Press SAVE to update the setting.
To set the keypad timeout:
1.
Scroll to the KEYPAD TIMEOUT programming
option.
2.
Press SELECT.
3.
Enter the preferred time (10-300 DAY).
4.
Press SAVE to update the setting.
To set the wireless fail to set (FTS) setting:
1.
Scroll to the WIRELESS FTS programming
option.
2.
Press SELECT.
3.
Enter the preferred time (0-720 min).
4.
Press SAVE to update the setting.
* Wireless features and devices will be available with a later market package.
To set the wireless lost setting:
1.
Scroll to the WIRELESS LOST programming
option.
2.
Press SELECT.
3.
Enter the preferred time (0-720 min).
*Wireless features and devices will be available with a later
market package.
To permit an engineer access to the system, use
this setting:
1.
Scroll to the ENGINEER ACCESS
programming option.
2.
Press SELECT.
3.
Enter the preferred time (0-999 min).
4.
Press SAVE to update the setting.
...MAINS SIG DELAY...
BACK
SELECT
14
(0-60) MIN
BACK
SAVE
...KEYPAD TIMEOUT...
BACK
SELECT
30
(10-100) DAY
BACK
SAVE
...WIRELESS FTS...
BACK
SELECT
0
(0-720) MIN
BACK
SAVE
...WIRELESS LOST...
BACK
SELECT
720
(0-720) MIN
BACK
SAVE
...ENGINEER ACCESS...
BACK
SELECT
30
(0-999) MIN
BACK
SAVE
09.2008