Led Indicators - Panasonic EBL128 Daily User's Manual

Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

2.1. LED INDICATORS

See reference picture on page 4.
1
Fire
2
Alarms queued
3
Extinguishing
4
Ventilation
5
Fire brigade tx
6
Operation
7
General fault
8
Disablements
9
Fault tx activated
10
Sevice
11
Alarm devices
12
Fire brigade tx
13
System fault
14
Fire brigade tx delay
15
Test mode
16
Door open
DAILY USER´S MANUAL
Fire alarms.
More than one alarm point / zone have activated fire alarm.
Output(s) for extinguishing equipment activated.
Output(s) for fire/smoke ventilation equipment activated.
Output "Fire alarm" for fire brigade tx (routing equipment) activated.
The c.i.e. is powered via the rectifier and/or the battery.
Fault(s) in the system.
Disablement(s) in the system.
Not acknowledged fault(s):
Output "Fault condition" for fault tx (routing equipment) is activated.
One or more sensors have reached the service level. See menu H4/U4.
Steady light: Output(s) type "Alarm device" are disabled.
Flashing light: Output(s) type "Alarm device" have generated fault(s).
Steady light: Output(s) for "Routing equipment" disabled via menu H2/B3 or
B9 or via open door.
Flashing light: Routing equipment power supply outputs or supervised
outputs of type "Routing equipment" have generated fault(s) or the c.i.e.
has lost contact with these outputs.
EBL128 is not running because of:
S/W fault
CPU fault
Memory fault
C.i.e. restart (fault code ≠ 00 / 03).
The Alert Annunciation function is enabled.
Zones are in "test mode".
The door is open in the EBL 128 or an external FBP in the system.
5
EBL128 VERSION 2.2.X
DOCUMENT NUMBER: MEW01786
REVISION: 1