6. PERFORM MONTHLY TEST (H1)

a) Log on to the c.i.e.
b) Press "A".
c) Check that all LEDs light up.
d) Press "A". The c.i.e. buzzer sounds, all the dots in the display are shown and all LEDs on the front
are turned on.
e) Press "A". Up to four zones can be set in test mode. Use the keypad to type the zone numbers.
f) Press "A".
g) Perform the test.
h) To end the test, press "A".
If the routing equipment shall not be tested, the monthly test is completed. Press "A".
If the routing equipment shall be tested, press "1". To start the test press "A".
Started test is indicated by LED "Fault tx activated" and after 30 seconds also LED "Fire brigade tx".
After 60 seconds in total, the routing equipment test is ended and the LEDs are turned off. Press "A".
DAILY USER´S MANUAL
9
EBL128 VERSION 2.2.X
DOCUMENT NUMBER: MEW01786
REVISION: 1