Device characteristics
Ambient conditions
Mechanical data
Standards
Building Technologies
Fire Safety & Security Products
Response sensitivity (typ.)
Permissible wind speed
Compensation speed
Detector diagnosis
CO sensor service life
Permitted ambient temperature
Storage temperature
Optimum storage temperature
Air humidity
Protection categories according to
EN 60529/IEC 60529:
Base FDB221/FDB222
Base attachment FDB291 with base
FDB221/FDB222
Base attachment humid FDB293 with
base FDB221/FDB222 and FDOOTC241
Sounder base FDSB29x
Electromagnetic compatibility:
1 MHz ... 2 GHz
Dimensions (Ø x H):
Weight
Colour
Standards
VdS approvals
LPCB approvals
FM approvals
Certificates
CE conformity mark
QA Standards
3 ... 12 %/m (depending on the parameter set)
Max. 20 m/s
≤ 1/45 voltage increase for detection/h
With detector exchanger and tester FDUD292
or
intelligent detector tester FDUD293
Max. 5 years
-20 ... +50 ℃
-20 ... +55 °C
0 ... +20 °C
15 ...90 % rel.
IP43
IP43
IP44
IP43
30 V/m
100 x 47 mm
0.106 kg
∼RAL 9010 pure white
CEA 4021
EN 54-7, EN 54-17, EN 54-5
VdS 2806
G209040
Pending
Pending
0786-CPD-20694
Yes
Siemens Standard SN 36350
ISO 9001, ISO 9004
Specifications