Toshiba RAV-SP1100UT-E Service Manual page 30

Hide thumbs Also See for RAV-SP1100UT-E:
Table of Contents

Advertisement

No.
Item
3
Room
temperature
control
4
Automatic
capacity control
(GA control)
5
Air speed
selection
Outline of specifications
1) Adjustment range Remote controller setup tem-
perature (°C)
COOL/
DRY
Wired type
18 to 29
Wireless type
18 to 30
*
: Only for 4-way air discharge cassette type
*
2) Using the item code 06, the setup temperature in
heating operation can be compensated.
Setup data
0
Setup temp.
+0°C
compensation
Setting at shipment
Setup data
2
1) Based on the difference between Ta and Ts, the
operation frequency is instructed to the outdoor unit.
1) Operation with (HH), (H), (L), or [AUTO] mode is
performed by the command from the remote controller.
2) When the air speed mode [AUTO] is selected, the air
speed varies by the difference between Ta and Ts.
<COOL>
Ta (˚C)
+3.0
HH
+2.5
(HH)
+2.0
H (HH)
+1.5
H (HH)
+1.0
L(H)
+0.5
L(H)
Tsc
L(H)
-0.5
L(L)
• Controlling operation in case when thermo of remote
controller works is same as a case when thermo of
the body works.
• If the air speed has been changed once, it is not
changed for 3 minutes. However when the air volume
is exchanged, the air speed changes.
• When cooling operation has started, the air speed
selects a downward slope, that is, the high position.
• If the temperature is just on the difference boundary,
the air speed does not change.
• Mode in the parentheses indicates one in automatic
cooling operation.
Heating
Auto
operation
operation
18 to 29
18 to 29
16 to 30
17 to 27
2
4
6
+2°C
+4°C
+6°C
A
B
C
D
E
F
G
30
Remarks
Shift of suction tempera-
ture in heating operation
HH > H > L > LL