Toshiba RAV-SP1100UT-E Service Manual page 13

Hide thumbs Also See for RAV-SP1100UT-E:
Table of Contents

Advertisement

RAV-SM800UT-E, RAV-SM801BT-E, RAV-SM801CT-E, RAV-SM800KRT-E / RAV-SP800AT-E
Outer diameter of refrigerant pipe
Gas side ØA
Liquid side ØB
15.9mm
9.5mm
TS sensor
TD sensor
Accumulator
(1500cc)
Rotary compressor
(DA220A2F-20L)
Pressure
(MPa)
Pd
Standard
2.72
Cooling
Overload
3.57
Low load
1.89
Standard
2.58
Heating
Overload
3.49
Low load
2.30
4 poles are provided to this compressor.
*
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
* The refrigerating cycle of the indoor units differs according to
the models to be combined. For the refrigerating cycles of the
other indoor units, refer to the corresponding Service Manuals
described in the list on the cover.
Refrigerant pipe
at gas side
Outer dia. ØA
Pd
Packed valve
Outer dia. ØA
Strainer
4-way valve
(STF-0213Z)
Muffler
Ø25 × L210
Ø25 × L160
Pipe surface temperature (°C)
Discharge
Suction
Ps
(TD)
(TS)
0.93
74
12
1.10
80
21
0.74
34
7
0.68
72
4
1.22
79
19
0.25
91
–17
Indoor unit
Air heat exchanger
TC sensor
Outdoor unit
TO sensor
TE
sensor
Heat exchanger Ø8
2 row 30 stages
FP1.3 flat fin
Indoor heat Outdoor heat
revolutions per
exchanger
exchanger
(TC)
(TE)
11
40
17
52
2
12
41
2
55
16
37
–19
13
TCJ
sensor
Refrigerant pipe
at liquid side
Outer dia. ØB
Packed valve
Outer dia. ØB
Modulating (PMV)
(SKV-18D26)
Strainer
Capillary
Ø3×Ø2×
L530
R410A 2.1 kg
Indoor/Outdoor
Compressor
temp. conditions
Indoor
(DB/WB) (°C)
fan
second (rps)
*
Indoor
55
HIGH
27/19
47
HIGH
32/24
24
LOW
18/15.5
62
HIGH
20/–
28
LOW
30/–
90
HIGH
15/–
Max.
50m
Ps
Cooling
Heating
Outdoor
35/–
43/–
–5/–
7/6
24/18
–15/
(70%)