2way valve for zone#1 (Floor heating)
N
PCB
T/B
Connecting a 2way valve for zone#1
1 . Directly connect a '2way valve for zone#1' with 'B11, B12, B13 and B14 ' in TB-B .
This port can supply power for small-medium sized valve .
Maximum current is 0 . 5 A
NOTE
Specification table
Terminal block (Output)
Connection load
Output (B11~B14)
1 . When the remote controller is used, floor valve should be connected to zone #1 and the FCU valve should be separately
connected to zone #2 of the control kit PBA .
2 . When only floor cooling/heating is installed and if the Water Law or outlet water temperature is too low, 2way valve may
closed and E911 error may occur .
3 . Samsung is not responsible for the accidents such as floor condensations which can occur by not connecting the valve to
the zone #1 port of the control kit PBA .
EHS Control unit_MIM-E03@_IM_E_34413-2.indd 23
2way valve for zone#1
L
B11
B12
Initially, the relay is connected between L and B14
Part
Relay
B13
B14
Specification
B11 : Output Power N
B12 : Output Power L
B13 : Output Power L (switched)
B14 : Output Power L (switched)
Direct connect 2way valves (under 0 . 5 A)
AC 230V (MAX 0 . 5 A / 120W)
23
2012-04-05 오후 1:20:05