Grounding the transmitter

Signal cable shield grounding
Signal cable shield grounding is summarized in
and unused shield drain wire must be trimmed and insulated, ensuring that the signal cable
shield and drain wire do not come in contact with the transmitter case. See
grounding" on page 62
below to correctly ground the signal cable shield.
1.
2.
3.
4.
5.
a.
6.
Figure 4-8. Wiring pair and ground
A. Insulate shield and shield drain wire
B. Insulate exposed shield drain wire
C. Terminate cable shield drain wire to earth ground
Electrical Installation
for instructions on grounding the transmitter case. Follow the steps
Remove the Field Terminals Housing Cover.
Connect the signal wire pair at the field terminals as indicated in
At the field terminals, the cable shield and shield drain wire should be trimmed close
and insulated from transmitter housing.
Reattach the Field Terminals Housing Cover; cover must be fully engaged to comply
with explosion proof requirements.
At terminations outside the transmitter housing, the cable shield drain wire should be
continuously connected.
Prior to the termination point, any exposed shield drain wire should be insulated as
shown in
Figure 4-8
(B).
Properly terminate the signal cable shield drain wire to an earth ground at or near the
power supply.