Floor Clearance Calculation Table - HP StorageWorks XP12000 Site Prep Manual

Hide thumbs Also See for StorageWorks XP12000:
Table of Contents

Advertisement

5.
To determine clearance A and clearance B, divide the A+B value between A and B.
They do not need to be equal. For example, if the A+B value from the table is 60
cm, then A can be 40 cm and B can be 20, or both A and B can be 30. However,
if your configuration includes only a DKC, or a DKC and one DKU, then A must be
at least 28 cm (11.1 in) to allow for opening the DKC front door.
6.
Calculate the floor clearance for the array using the following table.

Floor clearance calculation table

Clearance
values
Plus minimum
service
clearance
Equals minimum
floor clearances
34
Site requirements
Left
Right
(add down)
(add down)
B = _________+
A = _______+
10 cm
10 cm
(3.94 in)=
(3.94 in)=
Front
Back
(add down)
C = _________+
Not applicable
80 cm
80 cm
(31.5 in)=
(31.5 in)
80 cm (31.5 in)