Receptacles

Each disk array cabinet has two or four separate connections to AC power.
For disk array cabinets with two AC power connections, each input must be
capable of supporting the cabinet's entire current demand.
For disk array cabinets with four AC power connections, the two inputs to AC
Box 1 or the two inputs to AC Box 2 must be capable of supporting the cabinet's
entire current demand.

Fault tolerant AC power examples

When receptacles are used to connect disk array components to AC power, they must
include a dedicated ground connection that is insulated from the receptacle. It is
important that the receptacle box be grounded with an additional ground connection
that is separate from the dedicated ground. The additional ground can be hard conduit.
Specific power plugs and receptacles are required for the DKC and DKUs depending on
the power option you specify when ordering the HP XP12000 disk array. The power
cords on 60 Hz cabinets are shipped with plugs attached and connected. The power
cords on 50 Hz cabinets are shipped without plugs. You are responsible for having
the correct plugs and receptacles installed by an electrician in compliance with local
HP StorageWorks XP12000 Disk Array
53