Fisher FSKIF-121AE2-EU Service Manual page 129

Super dc inverter lcac series
Hide thumbs Also See for FSKIF-121AE2-EU:
Table of Contents

Advertisement

07
Condenser pipe temp.(T3)
08
Outdoor ambient temp.(T4)
09
Compressor discharge temp.(T5)
10
AD value of current
11
AD value of voltage
12
Indoor unit running mode code
13
Outdoor unit running mode code
14
EXV open angle
15
Frequency limit symbol
16
DC fan motor speed
17
IGBT radiator temp.
Indoor unit number
18
19
Condenser pipe temp. of 1# indoor unit
20
Condenser pipe temp. of 2# indoor unit
21
Reserved
22
1# Indoor unit capacity demand code
23
2# Indoor unit capacity demand code
24
Reserved
25
Indoor room temp. of 1# indoor unit
Electrical Control System
display tube will show "70". If the indoor unit is not connected,
the digital display tube will show: "――"
The display value is between 0~129 degree.If the temp. is
higher than 99 degree, the digital display tube will show single
digit and tens digit. (For example, the digital display tube show
"0.5",it means the compressor discharge temp. is 105 degree.
the digital display tube show "1.6",it means the compressor
discharge temp. is 116 degree)
The display value is hex number.
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4,
Dry:6,Self-clean:8, Forced defrosting:10
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4,
Dry:6,Self-clean:8, Forced defrosting:10
Actual data/4.
If the value is higher than 99, the digital display tube will show
single digit and tens digit.
For example ,the digital display tube show "2.0",it means the
EXV open angle is 120×4=480p.)
Frequency limit
Bit7
caused by IGBT
radiator
Frequency limit
Bit6
caused by PFC
Frequency limit
Bit5
caused by T4.
Frequency limit
Bit4
caused by T2.
Frequency limit
Bit3
caused by T3.
Frequency limit
Bit2
caused by T5.
Frequency limit
Bit1
caused by current
Frequency limit
Bit0
caused by voltage
0 : Off 1 Turbo 2 High 3 Medium 4.Low 5 Breeze 6
Supper breeze
The display value is between 0~130 degree..If the temp. is
higher than 99 degree, the digital display tube will show single
digit and tens digit. (For example, the digital display tube show
"0.5",it means the IGBT radiator temp. is 105 degree. the
digital display tube show "1.6",it means the IGBT radiator
temp. is 116 degree)
The indoor unit can communicate with outdoor unit well.
General:1, Twins:2
If the temp. is lower than 0 degree, the digital display tube will
show "0".If the temp. is higher than 70 degree, the digital
display tube will show "70". If the capacity demand is 0, , the
digital display tube will show "0. If the indoor unit is not
connected, the digital display tube will show: "――"(heating
T2 , cooling T2B)
Actual data*HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show "5.0",it means the capacity demand
is 15. the digital display tube show "60",it means the capacity
demand is 6.0). If the indoor unit is not connected, the digital
display tube will show: "――"
If the temp. is lower than -9 degree, the digital display tube will
show "9".If the temp. is higher than 70 degree, the digital
display tube will show "70". If the capacity demand is 0, , the
digital display tube will show "0. If the indoor unit is not
connected, the digital display tube will show: "――"
Electrical Control Function
The display value is hex
number. For example,
the digital display tube
show 2A,then Bit5=1,
Bit3=1, Bit1=1.
It means frequency limit
caused by T4,T3 and
current.