Wiring and Fitting Modules

4.4 Insertion and removal of fail-safe modules

4.4
Insertion and removal of fail-safe modules
Inserting and Removing Electronic Modules
In ET 200S, the same procedure is used to insert and remove both fail-safe modules and
standard modules on terminal modules (see ET 200S Distributed I/O System manual).
Inserting and Removing Electronic Modules during Operation
F-modules can be inserted and removed during operation in exactly the same way as
standard modules in ET 200S.
Note
Hot-swapping fail-safe modules in ET 200S during operation generates a communication
error on the F-CPU.
You must acknowledge this communication error in your safety program. (For information on
the response of the F-system after communication errors, output of a fail-safe value and user
acknowledgment, refer to the
F/FH Systems, Configuring and Programming)
If the communication error is not acknowledged, the useful data of the F modules remain
passivated (inputs and outputs in "0" state).
Conditions for Insertion and Removal during Operation
The table below lists the F-modules which support hot-swapping and the conditions under
which this is possible:
Table 4- 1
Module
Interface module
Fail-safe power module (PM E-F pm)
Fail-safe power module (PM E-F pp)
Fail-safe power module (PM D-F)
Fail-safe electronic module (F-DI)
Fail-safe electronic module (F-DI/DO)
Fail-safe electronic module (F-DO)
Fail-safe electronic module (F-RO)
Remember to Set the PROFIsafe Address
When replacing F-modules, ensure that the address switch (DIP switch) settings of the left of
the modules match.
36
S7 Distributed Safety, Configuration and Programming
Conditions for Hot-Swapping Fail-Safe Modules
.
Insertion and
Conditions
Removal
No
Yes
Load voltage must be switched off
Yes
Yes
Yes
Yes
Load voltage must be switched off
Yes
Load voltage must be switched off
Yes
Load voltage must be switched off
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07