Code Parameters
Electronic limit contact (binary output)
c21 Message in case of event
c22 Switching value
c23 Hysteresis
Electronic limit contact 1
c24 Message in case of event
c25 Switching value
c26 Hysteresis
Electronic limit contact 2
c27 Message
c28 Switching value
c29 Hysteresis
Input signal
c31 Detect input signal failure
c32 Reference value upon input
signal failure
c33 Internal travel value
c34 Travel for priority position
c35 End position guiding:
valve open
c36 End position guiding:
valve closed
c37 Position feedback indicates
error
Operation
c42 Operating direction
62
Setting range
(select ESC to cancel)
NONE (inactive),
HIGH (upper limit violation),
LOW (lower limit violation)
0.0 to 100.0 %
0.0 to 10.0 %
NONE (inactive),
HIGH (upper limit violation),
LOW (lower limit violation)
0.0 to 100.0 %
0.0 to 10.0 %
NONE (inactive),
HIGH (upper limit violation),
LOW (lower limit violation)
0.0 to 100.0 %
0.0 to 10.0 %
NO,
YES
INT (internal travel value),
LAST (last travel value)
0.0 to 100.0 %
0.0 to 100.0 %
0.0 to 100.0 %
0.0 to 49.9 %
YES (error reading active),
NO (error reading inactive)
>> (increasing/increasing),
<> (increasing/decreasing)
WE
Section
Customer
data
NONE
13.7
10.0 %
13.7
1.0 %
13.7
NONE
13.8
10.0 %
13.8
1.0 %
13.8
NONE
13.8
90.0 %
13.8
1.0 %
13.8
NO
13.2
INT
13.2
0.0 %
13.2
0.0 %
13.6
97.0 %
13.2
1.0 %
13.2
NO
13.5
>>
13.3