Step Component
2
Discharge
1. Detachment
cabinet
1) Remove the front panels and upper panel.
[Step.1]
2) Remove the screws of the discharge cabinet
(upper), top of the heat exchanger plate.
(M4×10, 1 ) (Fig. 2-1)
3) Remove the screws of the discharge cabinet
(upper) and discharge cabinet (lower).
(M4×10, 2 ) (Fig. 2-4)
4) Remove the screws of the discharge cabinet
(upper) and fi n guard (upper).
(M4×10, 3 ) (Fig. 2-3)
5) Remove the screws of the discharge cabinet
(upper) and inverter assembly.
(M4×10, 4 ) (Fig. 2-4)
* Remove the screws of the discharge cabinet
(lower) and partition plate.
(M4×10, 3 ) (Fig. 2-5)
6) Remove the screws of the discharge cabinet
(upper) and motor base.
(M4×10, 2 ) (Fig. 2-6)
7) As in steps 2) to 6), remove the discharge
cabinets (lower).
2. Attachment
1) Mount by reversing the detachment procedure,
attaching the lower and upper discharge
cabinets in order.
• Insert the hooking tabs into the holes in the
motor base and fix each discharge cabinet in
place with screws. (Fig. 2-7)
Procedure
Heat exchanger (upper)
screw (1 position)
(Fig. 2-1)
Motor base
screws (2 positions)
(Fig. 2-6)
Hooking tabs
(Fig. 2-7)
153
Remarks
(Fig. 2-2)
Discharge
cabinet (upper)
Discharge
cabinet (lower)
screws (2 positions)
(Fig. 2-4)
Fin guard screws
(3 positions)
Discharge
(Fig. 2-3)
cabinet (lower)
screws (3 positions)
bottom plate
screws (2 positions)
(Fig. 2-5)
Discharge
cabinet (upper)
Discharge
cabinet (lower)
Inverter assembly
screws (4 positions)