Toshiba MCY-MHP0404HS(J)-E Service Manual page 111

Hide thumbs Also See for MCY-MHP0404HS(J)-E:
Table of Contents

Advertisement

Check code
Location
Outdoor 7-segment display
Main
remote
detection
Check
Sub-code
controller
code
IPDU
F13
F13
I/F
F15
F15
I/F
F16
F16
I/F
F23
F23
I/F
F24
F24
Indoor
F29
unit
I/F
F31
F31
IPDU
H01
H01
IPDU
H02
H02
of
Description
System status
TH sensor trouble All stop
Outdoor
All stop
temperature
sensor wiring
trouble (TE, TL)
Outdoor
All stop
pressure sensor
wiring trouble
(PD, PS)
PS sensor trouble All stop
PD sensor trouble All stop
Other indoor
Stop of
trouble
corresponding
unit
Outdoor
All stop
EEPROM trouble
Compressor
All stop
breakdown
Compressor
All stop
trouble (lockup)
110
121
Check code detection
Check items (locations)
condition(s)
Sensor resistance is zero
Trouble in IGBT built-in
(short circuit).
temperature sensor
Replace A3-IPDU P.C.
board.
During compressor operation
Check installation of TE
in HEAT mode, TE
and TL sensors.
continuously provides
Check resistance
temperature reading higher
characteristics of TE and
than indicated by TL by at
TL sensors.
least specified margin for 3
Check for outdoor P.C.
minutes or more.
board (I/F) trouble.
Readings of high-pressure
Check connection of high-
PD sensor and low-pressure
pressure PD sensor
PS sensor are switched.
connector.
Output voltages of both
Check connection of low-
sensors are zero.
pressure PS sensor
connector.
Check for trouble in
pressure sensors PD and
PS.
Check for trouble in outdoor
P.C. board (I/F).
Check for troubled in
compressive output of
compressor.
Check 4-way valve trouble.
Output voltage of PS sensor
Check for connection trouble
is zero.
involving PS sensor and PD
sensor connectors.
Check connection of PS
sensor connector.
Check for trouble in PS
sensor.
Check for troubled in
compressive output of
compressor.
Check for trouble in 4-way
valve.
Check for trouble in outdoor
P.C. board (I/F).
Check for trouble in SV4
circuit.
Output voltage of PD sensor
Check connection of PD
is zero (sensor open-
sensor connector.
circuited).
Check for trouble in PD
Pd > 4.15 MPa despite
sensor.
compressor having been
Check for trouble in outdoor
turned off.
P.C. board (I/F).
Indoor P.C. board does not
Check for trouble in indoor
operate normally.
P.C. board (troubled
EEPROM)
Outdoor P.C. board (I/F)
Check power supply
does not operate normally.
voltage.
Check power supply noise.
Check for trouble in outdoor
P.C. board (I/F).
Inverter current detection
Check power supply voltage.
circuit detects overcurrent
(AC220-240V ± 10%).
and shuts system down.
Check for trouble in
compressor.
Check for possible cause
of abnormal overloading.
Check for trouble in outdoor
P.C. board (A3-IPDU).
Check miswiring,
misinstallation SV5.
Overcurrent is detected
Check for trouble in
several seconds after startup
compressor.
of inverter compressor.
Check power supply voltage.
(AC220-240V ± 10%).
Check compressor system
wiring, particularly for open
phase.
Check connection of
connectors / terminals on
A3-IPDU P.C. board.
Check for trouble in outdoor
P.C. board (A3-IPDU).