Design information
Combustion air supply via horizontal pipes
Rated heat-
System size
ing output
Flue sys-
range in
tem
8
kW
Vitocrossal 200, type CM2
80 to 87
DN 125
80 to 87
DN 150
105 to 115
DN 125
105 to 115
DN 150
130 to 142
DN 150
130 to 142
DN 200
170 to 186
DN 200
170 to 186
DN 200
225 to 246
DN 200
285 to 311
DN 250
Vitocrossal 300, type CT3U
370 to 400
DN 250
460 to 500
DN 250
375 to 630
DN 250
For routing through shafts or ducts with longitudinal ventilation
that meet the requirements for domestic chimneys to DIN V
18160-1, or have a fire rating of 90 min (L90).
4 6
1
A Ventilation air
B Flue gas
C Inspection port
D Minimum internal shaft dimension (see page 31)
VIESMANN
36
(cont.)
Max. height/length in m
Ventilation
Flue
Ventilation
air routing
air line
DN 150
25
DN 150
30
DN 150
10
DN 150
30
DN 150
28
DN 150
30
DN 150
30
DN 200
30
DN 200
26
DN 250
30
DN 250
30
DN 250
25
DN 250
8
B
A
2
3
4
3
2
3
2
2
3
5 C
A
3
D
The details apply subject to the following assumptions:
■ Length of the connection piece (flue): 2 m and 3 x 87° bends (includ-
ing support bends)
■ Length of the connection piece (ventilation air line): 2.5 m and 2 x
87° bends
Note
11
With the Vitocrossal 200 with MatriX radiant burner, a draught of 70
30
Pa is available for the balanced flue system.
5
30
Minimum distance for secondary ventilation between the internal
11
cross-section of the shaft and the female connection, see page 31.
30
For balanced flue operation, the Vitocrossal 200 requires a flue pipe
10
between the gas condensing boiler and the shaft (chimney) (type C
30
to TRGI 2008).
6
System size flue pipe 7 125, 150, 200 and 250 mm.
30
If the ventilation air supply is routed separately, use individual com-
ponents of the flue pipe size 7 150 or 200 mm.
30
A boiler flue connection must be ordered for the connection to the
15
Vitocrossal.
5
For system size diameter 125, 150, 200 and 250 mm
1
Boiler flue connection
(order separately)
Extension
2
Basic shaft unit
comprising
– Support bend
– Support rail
– Shaft cover
– Spacers (3 pce)
Spacers (3 pce)
3
Pipe
– 2 m long (2 pce = 4 m long)
– 2 m long (1 pce)
– 1 m long (1 pce)
– 0.5 m long (1 pce)
4
Inspection piece
Straight (1 pce)
5
Flue bend
87° (1 pce)
45° (2 pce)
Flue bend
(for use in corbelled chimneys)
30° (2 pce)
15° (2 pce)
6
Inspection bend
87° (1 pce)
Reducer
33
Gas condensing boilers

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents