Panasonic S-22MU1E5A Technical Data Manual page 26

Vrf systems indoor unit
Hide thumbs Also See for S-22MU1E5A:
Table of Contents

Advertisement

3. How to install the indoor unit
3-1-5-2. Installing the Drain Pipe
CAUTION
Do not apply force to the drain port when connecting the
drain pipe. Install and fix it near the indoor unit as close
as possible.
Do not use adhesive when connecting the drain port pipe
and the drain hose.
(1) How to Install the Drain Pipe
1)
First insert the supplied hose band into the drain port
pipe. Then make sure the head of the screw is facing
toward a technical engineer when placing the screw of
1
the hose band at an upward angle.
2)
Insert the soft PVC socket of the supplied drain hose
to the drain port pipe. Do not use adhesive when
connecting the drain hose to the drain port pipe.
Insert it until the tip of the drain hose contacts the circular
2
projection rib of the drain port pipe.
3
(Drainage check section
on drain port, transparent)
4
5
Do not make hose band overlap the circular projection
rib and the sealed circulation projection of the drain
port pipe. (Torque: 2.5 N·m - 3.4 N·m)
6
7
Circular projection rib
8
* After checking the drainage, wrap the supplied packing and drain pipe insulator around the pipe.
9
Circular
Drain port
projection rib
Indoor unit
Do not use adhesive here.
* Drain port may possibly be damaged if
PVC adhesive is used.
Indoor unit
3)
Move the hose band so that the center position of the
hose band can be placed approx. 30 mm away from the
external plate of the indoor unit. (Fig. 2-28)
4)
Screw the drain hose tightly facing the screw of the hose
band upward. (Torque: 2.5 N·m - 3.4 N·m) (If the screw
is tightened beneath the drain hose, the troubles will be
occurred.) Pay attention not to make hose band overlap
the circular projection rib and the sealed circulation
projection of the drain port pipe.
5)
Apply approx. 2
hose without connection of the hard PVC socket and the
hard PVC joint (VP25) in the local supply.
6)
Connect the drain hose and the hard PVC joint so that
the adhesive area of both sides can be overlapped.
Wipe off the protrusion-adhesive with a soft cloth.
Hose band (supplied)
Soft PVC socket
Drain hose
(supplied)
Sealed
circulation
projection
rib
Adhere with PVC adhesive.
* Apply approx. 2 g of adhesive on both sides of the
drain hose without connection of the hard PVC
socket and the hard PVC joint (VP25) in the local
supply. Wipe off the protrusion-adhesive with a soft
cloth.
57 mm
20 mm or more
* However, do not use the hard PVC
Sealed circulation
projection rib
Approx. 5 mm
Approx. 30 mm
2-18
Design of VRF SYSTEM
g of adhesive on both sides of the drain
Hard PVC socket
Hard PVC pipe
(VP25 field supplied)
Note:
Be sure to tightly insert the hard PVC
pipe joint (including elbow) minimum
20 mm or more.
pipe joint allowable more than 55 mm
insertion.
Drain insulator (supplied)
Packing (supplied)
Fig. 2-28

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents