A.O. Smith Innovo 12-160 Installation, Service & Maintenance Manual page 72

Condensing high-efficiency water heater
Table of Contents

Advertisement

Indication
Water leakage
Explosive ignition
Insufficient or no hot
water
72
Cause
There is a leakage from a threaded
water connection.
There is a condensate leakage
There is a leakage from another nearby
water heater or pipe segment.
There is a leakage from the water heater
tank.
The gas supply pressure is incorrect.
The CO
value is incorrect.
2
The burner is contaminated.
There is an air leakage between the
venturi and the flexible air connector.
The water heater is off.
There is no supply voltage.
The hot water supply is used up.
The controller is in the OFF mode.
The temperature (T
) is set too low.
set
Measure
Tighten the threaded connection.
Make sure that the condensation water
discharge is working properly.
If necessary, correct the water discharge.
Trace the leakage.
Contact the supplier of your water heater.
Check the gas supply pressure, refer to Gas
supply pressure (see section 8.9.3).
Check the CO2 value, refer to CO
(see section 8.9.4).
Clean the burner, refer to Gas-side
maintenance (see section 11.4).
Make sure that:
the flexible air connector is not damaged.
If necessary, replace the flexible air
connector.
the flexible air connector is correctly
connected to the venturi.
If necessary, tighten the clamp.
Turn on the water heater (see section 4.2).
Make sure that:
the control switch is set to I.
the isolator is in ON position.
there is power on the isolator.
there is power to the electrical connector
block.
The measured voltage must be
230 V
(-15%, +10%).
AC
Reduce the hot water consumption. Wait
until the water heater heats up.
Set the controller in the ON mode (see
section 4.2.1).
Set the temperature (T
) to a higher value
set
(see section 4.2.2).
Installation, Maintenance and Service part
value
2