The length of the air inlet and flue gas outlet is the same for C43, C53 and C63 systems as
for C13 and C33 systems:
Refer to C13/C33 concentric systems (see section 8.7.1) for the maximum pipe
lengths of concentric systems.
Refer to C13/C33 parallel systems (see section 8.7.2) for the maximum pipe lengths
of parallel systems and non-concentric systems.
Note
Only use a C43 venting system when the common duct is a natural draught chimney. The
common duct is part of the building, not a part of the system.
Note
In a C53 venting system the flue gas terminal must be CE approved and must comply to
the EN 1856-1 requirements.
Note
Connect a C63 venting system to a separately approved and marketed system for the
supply of combustion air and discharge of flue gasses.
The flue gas terminal must comply to the EN 1856-1 requirements. The maximum
allowable recirculation rate is 10% under wind conditions.
Contact A.O. Smith for more information and/or part numbers of the C43, C53 and C63
venting systems.
Concentric systems
Refer to the table for the correct pipe dimensions of the C43, C53 and C63 concentric
systems.
Description
Manufacture venting material
Construction
Material flue gas outlet
Material air inlet
Diameter flue gas outlet
Diameter air inlet
Refer to C13/C33 concentric systems (see section 8.7.1) for the A.O. Smith part numbers.
The same parts can be used for the C43, C53 and C63 concentric systems.
Parallel and non-concentric systems
Refer to the table for the correct pipe dimensions of the C43, C53 and C63 parallel
systems.
Description
Manufacture venting material
Construction
Material flue gas outlet
Material air inlet
Diameter flue gas outlet
Diameter air inlet
Refer to C13/C33 parallel systems (see section 8.7.2) for the A.O. Smith part numbers.
The same parts can be used for the C43, C53 and C63 parallel systems.
Venting material
Venting material
PP
Alu
Muelink & Grol
Muelink & Grol
Concentric
Concentric
PP - Temp. Class T120 Thick walled aluminum
Thin walled galvanized
Thin walled galvanized
steel
steel
+0,6
80
/
mm
80
-0,6
+0,5
124
/
mm
124
-1
(Dn 125)
(Dn 125)
Venting material
Venting material
PP
Alu
Muelink & Grol
Muelink & Grol
Parallel
Parallel
PP - Temp. Class T120 Thick walled aluminum
+0,6
80
/
mm
80
-0,6
Installation, Maintenance and Service part
+0,3
/
mm
-0,7
+0,5
/
mm
-1
+0,3
/
mm
-0,7