QuickSpecs
Technical Specifications
System Inlet
Temperature
Relative
Humidity
(non-
condensing)
Altitude
Acoustic
Noise
Standard
10° to 35°C (50° to 95°F) at sea level with an
Operating
altitude derating of 1.0°C per every 305 m (1.8°F
Support
per every 1000 ft) above sea level to a maximum of
3050 m (10,000 ft), no direct sustained sunlight.
Maximum rate of change is 20°C/hr (36°F/hr). The
upper limit and rate of change may be limited by the
type and number of options installed. System
performance during standard operating support may
be reduced if operating with a fan fault or above
30°C (86°F).
Extended
For approved hardware configurations, the
Ambient
supported system inlet range is extended to be: 5°
Operating
to 10°C (41° to 50°F) and 35° to 40°C (95° to
Support
104°F) at sea level with an altitude derating of
1.0°C per every 175 m (1.8°F per every 574 ft)
above 900 m (2953 ft) to a maximum of 3050 m
(10,000 ft). The approved hardware configurations
for this system are listed at the URL:
http://www.hp.com/servers/Ashrae
For approved hardware configurations, the
supported system inlet range is extended to be: 40°
to 45°C (104° to 113°F) at sea level with an altitude
derating of 1.0°C per every 125 m (1.8°F per every
410 ft) above 900 m (2953 ft) to a maximum of
3050 m (10,000 ft). The approved hardware
configurations for this system are listed at the URL:
http://www.hp.com/servers/Ashrae
System performance may be reduced if operating
in the extended ambient operating range or with a
fan fault.
Non-operating
-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).
Operating
10% to 90% relative humidity (Rh), 28°C (82.4°F)
maximum wet bulb temperature, non-condensing.
Non-
5 to 95% relative humidity (Rh), 38.7°C (101.7°F)
operating
maximum wet bulb temperature, non-condensing.
Operating
3048 m (10,000 ft). This value may be limited by the type
and number of options installed. Maximum allowable
altitude change rate is 457 m/min (1500 ft/min).
Non-
9144 m (30,000 ft). Maximum allowable altitude change
operating
rate is 457 m/min (1500 ft/min).
Listed are the declared A-Weighted sound power levels (LWAd) and
declared average bystander position A-Weighted sound pressure
levels (LpAm) when the product is operating in a 23°C ambient
environment. Noise emissions were measured in accordance with ISO
7779 (ECMA 74) and declared in accordance with ISO 9296 (ECMA
109).
Idle
L WAd
6.8 B
L pAm
51.2
Operating
L WAd
6.9 B
DA - 15296 Worldwide QuickSpecs — Version 10 — 6.20.2016
HPE ProLiant DL560 Generation9 (Gen9)
Page 53