FRU Removal and Replacement
14. If necessary, close and lock the equipment cabinet door.

RRP: Redundant Fan Module

Use the following procedures to remove or replace a redundant cooling fan
module. A list of tools required is provided.

Tools Required

The following tools are required to perform these procedures.

Removing the Fan Module

To remove a redundant fan module:
1. If the director is installed in a stand-alone configuration, go to
2. Follow ESD procedures by attaching a wrist strap to the director chassis and
3. Remove the RFI shield.
4. Identify the defective fan module from the amber LED on the module or
5. Two captive screws secure the fan module (1) to the director chassis, as
250
b. Click the Sys Err Light tab. The Switch page displays with the Sys
Err Light tab selected. A System Error Light is ON
message displays on the page.
c. Click Clear Light.
Standard flat-tip screwdriver.
ESD grounding cable and wrist strap.
director is rack-mounted, unlock and open the cabinet rear door as directed by
the HP authorized service provider.
your wrist, as shown in
Caution:
To avoid causing machine errors or damage while working on the
director, follow ESD procedures by connecting a grounding cable to the
director chassis and wearing an ESD wrist strap.
failure information at the Hardware View.
shown in
Figure
80. Using a standard flat-tip screwdriver, loosen the captive
screws.
Figure
73.
step
2. If the
Director 2/140 Service Manual