Response Times - Mitsubishi FX1S-10MR-ES/UL Hardware Manual

Fx1s series
Table of Contents

Advertisement

FX1S Series Programmable Controllers
Outputs 6
6.3

Response Times

OFF times increase as the load current decreases.
For improved response times use a 'dummy' resistor, see Figure 6.2. If a response time of 0.5
ms or better is required when using 'light loads' use a 'dummy' resistor and ensure the signal
line has a current greater than 60mA/24V DC.
Figure 6.2: Dummy load
+V
Y
5 to 24V
Dummy load
Load
Y000 and Y001 are high speed response outputs with the following characteristics:
10 - 100 mA at 5 - 24V DC, 100 kHz maximum output signal.
If the high speed response is required, a current of 10 - 100mA must be used.
6-4