Addressing
CPU 313C-2 PtP/DP
The following addresses are assigned to the integrated I/O of CPU 313C-2 PtP/DP:
Table 8-5
Inputs/Outputs
16 digital inputs
16 digital outputs
CPU 314C-2 PtP/DP
The following addresses are assigned to the integrated I/O of CPU 314C-2 PtP/DP:
Table 8-6
Inputs/Outputs
24 digital inputs
16 digital outputs
4 +1 analog inputs
2 Analog outputs
Remarks
You cannot influence outputs with transfer instructions if they are assigned to
technological functions.
I/O not configured for technological functions can be used as standard I/O.
8-10

Integrated inputs and outputs on the CPU 313C-2 PtP/DP

Default: addresses
124.0 to 125.7
of those are 12 Inputs for
technological functions:
124.0 to 125.0
125.4 to 125.6
124.0 to 125.7
of those are 3 Inputs for
technological functions:
124.0 to 124.2

Integrated inputs and outputs on the CPU 314C-2 PtP/DP

Default: addresses
124.0 to 126.7
of those are 16 Inputs for
technological functions:
124.0 to 125.7
124.0 to 125.7
of those are 4 Inputs for
technological functions:
124.0 to 124.3
752 to 761
752 to 755
S7-300 Programmable Controller Hardware and Installation
Remarks
All digital inputs can be programmed
as interrupt input.
Optional technological functions:
Counting
Frequency measurement
Pulse width modulation
Remarks
All digital inputs can be programmed
as interrupt input.
Optional technological functions:
Counting
Frequency measurement
Pulse width modulation
Positioning
A5E00105492-02