FX2N-32DP-IF Profibus-DP Interface Unit
C-2-16: FX
-1HC Short Configuration
2N
Requirements:
• Cyclic data is 8 word inputs and 8 word outputs in every cycle.
Table C-34: Cyclic Data of FX
1st
2nd
3rd
4th
5th
6th
7th
8th
• Parameter is 35 bytes.
2N
Send Data
Preset data lower word (BFM #10)
Preset data upper word (BFM #11)
YH compare value lower word
(BFM #12)
YH compare value upper word
(BFM #13)
YS compare value lower word
(BFM #14)
YS compare value upper word
(BFM #15)
Up/down command (BFM #1)
Command (BFM #4)
-1HC Short Configuration
Compare results (BFM #26)
Terminal status (BFM #27)
Current counter value lower word
(BFM #20)
Current counter value upper word
(BFM #21)
Maximum counter value lower word
(BFM #22)
Maximum counter value upper word
(BFM #23)
Minimum counter value lower word
(BFM #24)
Minimum counter value upper word
(BFM #25)