Connecting up

This section provides information on the terminal assignment of the individual interfaces and
the block diagram of the CPU 1516-3 PN/DP.
24 V DC supply voltage (X80)
The connector for the power supply is plugged in when the CPU ships from the factory.
The following table shows the pin assignment for a 24 V DC power supply.
Bridged internally:
and
and
Figure 3-1
If the CPU is supplied by a system power supply, it is not necessary to connect the 24 V
supply.
28
+24 V DC of the supply voltage
Ground of the supply voltage
Ground of the supply voltage for loop-through (maximum of 10 A permitted)
+24 V DC of the supply voltage for loop-through (maximum of 10 A permitted)
Spring opener (one spring opener per terminal)
Supply voltage connection
CPU 1516-3 PN/DP (6ES7516-3AN01-0AB0)
Manual, 09/2016, A5E03461313-AD