The gas control valve has been preset at the factory.
Altering settings may result in fire hazard or bodily
injury.
3. Gas Pressure
On the standing pilot and electronic gas control valve, a pressure tap is included on the front face of the valve.
Pressure taps are located on the front face of the valve and accessible for test gauge connection.
Tables 2 and 3 show optimum gas pressure information. Consult your local gas company for assistance in
determining the proper orifice for your altitude or refer to ANSI Z223.1-latest edition, Appendix F.
4. Gas Conversions
Natural or propane gas conversions necessary to meet the application need to be made by a qualified technician
using Hearth & Home Technologies specified and approved parts. In the event your gas appliance must be converted
to use: Propane/standing pilot - CKVP, Natural Gas/standing pilot - CKVN; Propane/intermittent pilot - DCKVP, Natural
Gas/intermittent pilot - DCKVN.
f i r e - p a r t s . c o m
Inlet Gas Supply Press. (N.G.)
Optimal Manifold Press (N.G.)
Inlet Gas Supply Press. (L.P.)
Optimum Manifold Press. (L.P.)
Table 2 - Gas Information for Intermittent Pilot
and Standing Pilot Appliances
12
WARNING!
CALIBER 60 and 80
4.5 (min.) - 7.0 (max.) in. w.c.
3.5 in. w.c.
11.0 (min.) - 14.0 (max.) in. w.c.
10 in. w.c.
CALIBER B-VENT INSTALLATION INSTRUCTIONS
Note:
The gas appliance and its manual shutoff valve
must be disconnected from the gas supply piping sys-
tem during any pressure testing of that system at test
pressures in excess of 1/2 psi (3.5 kPa). The gas appli-
ance must be isolated from the gas supply piping sys-
tem by closing its manual shutoff valve during any pres-
sure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psi (3.5 kPa).
CALIBER:
Input Rate (N.G.)
Input Rate (L.P.)
Orifice Size (N.G.)
Orifice Size (L.P.)
Table 3 - Gas Information for Intermittent Pilot
and Standing Pilot Appliances
31282 Rev Q
60
80
32,000 BTU/hr.
35,000 BTU/hr.
32,000 BTU/hr.
35,000 BTU/hr.
.110 in.
.113 in.
.067 in.
.070 in.
09/04