UTICA BOILERS STARFIRE 3 WATER Installation, Operation & Maintenance Manual page 19

Oil fired cast iron boiler
Table of Contents

Advertisement

2.
Primary control and flame sensor check following:
A.
flame failure
- simulate by shutting off oil supply
with hand valve while burner is on. Sixty seconds
after flameout, the safety switch locks out, ignition
stops, motor stops and oil valve - when used -
closes. To restart, open oil supply valve and reset
safety switch.
B.
Ignition failure
valve and run through start-up procedure, The
safety switch should lock out as in flame failure.
C.
Power failure
- Turn off main power supply switch
while burner is operating. When burner stops,
restore power and burner should start.
If operation is not as described as above, check
wiring and controls.
Preventive maintenance - of oil fired boiler reduces
operating costs. Boiler and vent pipe should be
inspected for accumulation of soot or scale deposits
periodically but at least once every year before start
of each heating season. When soot is present on
section walls and flueways, improper combustion will
result, causing additional sooting and scaling until
flueways are completely closed. To remove soot and
scale from flueways, remove top jacket panel, top
clean-out plate, open burner swing door.
#19)
Periodic Inspection - and tightening of tankless
heater/cover plate bolts will reduce risk of leaks. See
Replacement Parts "Heat Exchanger" section.
• Use only number 2 fuel oil.
• Do not use gasoline, crankcase drainings or
!
any oil containing gasoline.
• Do not attempt to start burner when excess
oil has accumulated, when unit is full of vapor
or when combustion chamber is very hot.
OPERATING INSTRUCTIONS
- with burner off, close oil supply
(See figure
WARNING
Instructions for opening burner Swing Door
Turn off power to boiler.
1.
2.
Allow boiler to cool down.
3.
Disconnect power cable at factory supplied burner
electrical disconnect. See figure #19
4.
Loosen screws on the sides of lower front jacket panel.
See figure #19.
Pull bottom part of lower front panel forward.
5.
6.
Lift lower front panel up and off boiler. See
#19.
7.
Close oil valve. See
8.
Disconnect oil line from burner.
Do not try to swing door with oil line attached.
9.
10.
Remove nut from swing door stud on right hand side of
door.
Swing open burner and door to the left.
11.
Using flue brush, brush soot and scale into
combustion space where it can be removed through
swing door opening.
It is recommended to replace nozzle at start of each
heating season. Lubricate burner motor and circulator
motor - if required - with few drops of good grade
light motor oil. Do not over oil. Have competent
service person service burner and check controls and
check electrodes for carbon or cracks in insulators.
Burners should be adjusted to produce conditions
shown in Start-up and Adjustment of Oil Burner
procedure covered earlier in this section.
Use caution when vacuuming in the chamber
area. Damage to chamber could result.
19
figure
figures #15 & #16.
NOTICE