The CPU switches to "STARTUP" mode if:
The hardware configuration and program
blocks are consistent.
You set the CPU to "RUN" mode via the
programming device or the display and
the mode switch in is RUN position.
or
You set the mode switch from STOP to
RUN.
The CPU returns to the "STOP" mode in the
following cases of "STARTUP":
The CPU detects an error during startup.
You set the the CPU to "STOP" via the
programming device, display or mode
selector.
A STOP command is executed in the
Startup OB.
The CPU goes to the "RUN" mode in the
following cases of "START-UP":
The CPU has initialized the PLC tags.
The CPU has executed the startup
blocks successfully.
The CPU returns to the "STOP" mode in the
following cases of "RUN":
An error is detected that prevents con-
tinued processing.
A STOP command is executed in the
user program.
You set the the CPU to "STOP" via the
programming device, display or mode
selector.
10.5 Operating modes of the CPU
Effects
Non-retentive memory is cleared, and the content
of non-retentive DBs is reset to the start values of
the load memory. Retentive memory and reten-
tive DB contents are retained.
Commissioning
175