Gas Feeding Line; Gas Pressure - Riello RS 300/E LN Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

4.10.2 Gas feeding line

It must be type-approved according to required standards and is
supplied separately from the burner.
8
10
9
Vent
6
3
11
5
4
D3776
Key to lay-out (Fig. 20)
1
Gas input pipe for main burner
2
Manual valve
3
Low gas pressure switch
4
Safety shut-off valve
5
NO vent valve
6
Regulating shut off valve
7
Gas input pipe for pilot
8
Gas adjustment butterfly valve
9
Burner
10
High gas pressure switch
11
Manual valve (for seal control)
12
Pilot regulator
20008423
5
12
2
4
4
Vent
M ai n
1
gas suppl y
2
Fig. 20

4.10.3 Gas pressure

Important
The pressure at the head of the burner from table refers to zero
in the combustion chamber; to obtain true pressure, measured
by a U-type manometer, (Fig. 36) add the counter-pressure of
the boiler.
Note
See the accompanying instructions for the adjustment of the gas
train.
7
GCV
MBtu/hr
5112
5680
7574
9467
11361
13254
14390
6816
7574
9467
11361
12307
13254
15148
17042
9467
11361
13254
15148
17042
18935
19692
23
GB
Combustion
Gas butterfly +
Head
Adaptor
"WC
"WC
3.3
0.63
3.7
0.79
4.9
1.38
5.4
2.13
5.9
3
7.9
4.2
9
5.1
2.3
1.1
3
1.38
4.7
2.13
6.4
3
7.3
3.62
8.3
5.17
10.8
5.47
13
7
4.4
1.81
6
2.64
7.7
3
9.7
3.82
11.8
4.64
14.1
5.55
15
5.9