Electrode Positioning; Combustion Head Setting - Riello RS 300/E LN Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

4.7

Electrode positioning

Make sure that the electrode and the ignition pilot are positioned
as shown in figure (Fig. 15).
2"
PILO T
D9159
N° Hole
4
3
2
1
0
4545
4
3
2
1
0
3030
D9402
20008423
E LE CT R O DE
RS 300/E LN
6060
7575
9090
10605
4545
6060
7575
9090
Installation
4.8

Combustion head setting

In addition to varying air flow depending on the output request-
ed, the air gate valve servomotor 4) (Fig. 5) by means of a lifting
assembly - varies the setting of the combustion head.
This system allows an optimal setting even at a minimum firing
rate.
7/32"
For the same servomotor rotation, combustion head opening
can be varied by moving the tie rod onto holes 1-2-3, Fig. 16.
3
2
1
Fig. 15
The choice of the hole (1-2-3) to be used is decided on the basis
of diagram (Fig. 17) against the required maximum output.
Setting is pre-arranged in the plant for the maximum run (hole 3)
(Fig. 16).
When dealing with boilers featuring a strong back pressure, if air
delivery is insufficient even with the damper fully open, you can
use a different setting to that illustrated in diagram (Fig. 17) do
this by moving the tie rod onto the next highest hole numerically
speaking, thus increasing the combustion head's opening and
hence air delivery.
RS 400/E LN
12120
13635
15150
RS 500/E LN
10605
12120
13634
15149
Max burner output
21
GB
D3093
M Bt u/ hr
16664
M Bt u/ hr
16664
18179
19694
0
4
Fig. 16
Fig. 17