I/O Calibration
PPO Motor Calibration
Step
7
Select "Save Cal". The following information will appear in a popup:
Feedback At 0%
Feedback At 100% - a value corresponding to the motor's 100% position [0.0 to 1.0]
Motor Speed (In Seconds). This is the motor speed that was detected during Motor Speed
Calibration. This is the time it takes the motor to travel from its calibrated 0% position to its
calibrated 100% position.
Select OK to save calibration, else select Cancel.
Status – Wait...Saving Calibration Values.
Percent Complete – indicates the progress of this step [0 to 100%]
Status – Calibration Complete
8
Once calibration is completed, select one of the following choices from the Motor Position
popup: Position Motor at 0%, Position Motor at 100, Don't Move Motor.

Hand Calibration Procedure

ATTENTION
The steps of the Hand Calibration Procedure must be performed in the order described below.
You must wait for each step to complete before selecting and activating the next step.
Step
1
Select block for calibration.
Select "Hand".
Status - Ready
2
Select "Start"
Status – Please Move Motor To 0% Position.
Feedback Value – indicates movement and direction of the motor [0.0 to 1.0]. This value
should increase when the motor is moved in the forward direction, and decrease when the
motor is moved in the reverse direction.
Percent Complete – will remain at 0% during this step.
Move the motor by hand to the 0% position. When complete, go to step 3.
3
Select "Calibrate 0%"
Status – Wait...Calculating 0% Feedback Value.
Feedback Value – indicates the current position of the motor [0.0 to 1.0]
Percent Complete – indicates the progress of this step [0 to 100%]
Status – 0% Feedback Value Captured
4
Status – Please Move Motor To 100% Position.
Feedback Value – indicates movement and direction of the motor [0.0 to 1.0]. This value
should increase when the motor is moved in the forward direction, and decrease when the
motor is moved in the reverse direction.
Percent Complete – will remain at 0% during this step.
Move the motor by hand to the 100% position. When complete, go to step 5.
170
Action
- a value corresponding to the motor's 0% position [0.0 to 1.0]

Table 42 Hand Calibration Procedure

Action
900 Control Station User Guide
Revision 9
May 2014