The 'System Values' Menu [/Welcome/Measurements/System Values] - ABB PQFS Installation, Operation And Maintenance Instructions

Power quality filter
Table of Contents

Advertisement

Q
S
cos j
PF
T IGBT
T Control
V dc bus
On the display, the parameters are organized in such a way that a maximum of
information is obtained without having to scroll down. The user may customize the display
to his particular needs. To do this, follow the steps given below:
· Select the measured parameter that has to be moved
· Press
· Press
· Once the selected parameter is located at the desired position in the list, press
Remark: During the display customization process, the
back to the original situation.
7.6.2

The 'System values' menu [/Welcome/Measurements/System values]

The 'System values' menu
parameters:
· The voltages: (Refer to
o
o
kW,
P > 0: Load absorbing active power
MW
P < 0: Load generating active power
var,
Reactive power in the network at the location of the CTs
kvar
Q > 0: Inductive reactive power
Mvar
Q < 0: Capacitive reactive power
VA,
Apparent power in the network at the location of the CTs
kVA,
MVA
-
Displacement power factor: calculation based on the
fundamental values of the measurements.
cos j > 0: load absorbing active power
cos j < 0: load generating active power
-
Power factor: calculation based on the fundamental and the
harmonic values of the measurements. Measurement only
valid for quasi-balanced loads.
°C/°F
IGBT module temperature (hottest module)
°C/°F
Main control board temperature
V
Active filter DC capacitor voltage
. The selected parameter starts flashing
or
to move the selected parameter up or down the list
(Figure
61) gives detailed information on the following
Table 34
Vrms, V1 and THDV in table format
The network voltage waveforms for all phases
All waveforms are synchronized with the rising edge zero crossing of
the voltage V (L1-N) (4-W mode) or V (L1-L2) (3-W mode)
Manual Power Quality Filter PQFS ç The PQF-Manager user interface 79
: System has inductive behavior
: System has capacitive behavior
key cannot be used to revert
for an explanation of the symbols).
(Figure
67)

Advertisement

Table of Contents
loading