ABB PQFS Installation, Operation And Maintenance Instructions page 45

Power quality filter
Table of Contents

Advertisement

Appropriate torque (20Nm) must be applied to ensure that cables are properly fixed.
7.
Slide the bottom protective cover up and fix it with the screws to seal off the power
supply terminals
8.
In addition to the power cables and the earth connection cable, the CT connection
cable and any other control cables used for enhanced functions can at this stage be
passed through the protective cover into the filter panel.
9.1 Preparation of the filter for networks of nominal voltage 380-415V:
When the filter will be installed on a network with nominal voltage 380-415V, no
further hardware configuration is needed. The two wires 'N' are by default connected
to the terminal block X02-1 (Cf.
Figure 34: Position of the wires 'N' for networks with nominal voltage 380-415V
9.2 Preparation of the filter for networks of nominal voltage 208-240V:
When the filter will be installed on a network with nominal voltage 208-240V, the
wires labeled 'N' (see
and have to be connected to the terminal X02-3 (see
Figure 35: Position of the wires 'N' for networks with nominal voltage 208-240V
Remark: the other wires labeled 'N' and also on the terminal X02-1 but on the other side
cannot be removed (see
Figure
34).
Figure
34) have to be disconnected from the terminal X02-1
Figure
36).
Manual Power Quality Filter PQFS ç Electrical design and installation 45
Figure
35).

Advertisement

Table of Contents
loading