ABB PQFS Installation, Operation And Maintenance Instructions page 106

Power quality filter
Table of Contents

Advertisement

SPI Timeout
Mismatch between units
Remark: Maximum limits for certain parameters are given in
Table 47
µcontroller fault message
Com. Problem 1 (CAN bus)
Com. Problem (RS-232)
Corrupted DSP code
Corrupted uC code
Internal uC fault
Ctrl over temperature
DSP watchdog
mController watchdog
SPI Time out
Flash memory corrupted
Power supply fault
Preload time-out
Real time clock problem
Several units same id
Different firmwares
For guidelines on how to troubleshoot and solve the reported problems, refer to
Chapter
Remarks:
106 The PQF-Manager user interface ç Manual Power Quality Filter PQFS
rotation.
Internal system error
Different units in a filter system have different settings (e.g. 3-
wire and 4-wire setting) or are connected in a different way.
gives an overview of the faults that can be reported by the µcontroller.
Table 47: Overview of the faults that can be reported by the
11.
· For multi-unit filters, this data can be obtained for each individual unit.
· Internal system errors are most likely due to faulty hardware and thus the only
solution may be to exchange the controller cards.
· If the message 'IGBT check cooling' appears, this implies that the system is
stopped due to an over temperature problem.
In that case, check the cooling of the system (fans, filters) and of the switchgear
room (air conditioning system etc.)
Description
Communication problem between different units in a multi-
unit filter arrangement
Serial communication problem between the main
controller board and an external PC
Internal system error
Internal system error
Internal system error
The system detected an over temperature of the main
controller board
Internal system error
Internal system error
Internal system error
Internal system error
Internal system error
The DC capacitors could not be preloaded in an
acceptable time
Internal system error
Two or more units have the same CAN_ID (settings of the
S5 dip switches (1 tot 3) on the control board
Different units in a filter system have different control
firmwares (DSP and/or microcontroller)
Table 24
m
controller

Advertisement

Table of Contents
loading