Chapter 7 Setting
7.1 Installation of the GSDML File
It is necessary to install the GSDML File to your PC tool (Engineering tool) of PROFINET IO controller
to use WJ-PN. GSDML file is a file that contains specific information of the PROFINET IO devices.
Please inquire to the nearest business contact about the GSDML file.
7.2 Parameter settings of WJ200 / WL200
WJ-PN needs the parameter settings of WJ200 / WL200, which shows the following table.
Concerning the operating of the system, it is necessary to refer to the instruction manual of the
inverter and the QRG of this option. Please perform appropriate settings as needed.

Parameter settings

Function
code
A001
Frequency source
A002
Run command source
A004
Maximum frequency
A038
Jog frequency
A039
Jog stop mode
Name
Value and description
04: option
04: option
Optional
Settable from the base
frequency to 400(580) Hz
Optional
Defines limited speed for
jog, range is from start
frequency to 9.99 Hz
Optional
Define how end of jog
stops
options:
00 : Free-run stop (invalid
during run)
01
deceleration
during run)
02 : DC braking to stop
(invalid during run)
03 : Free-run stop (valid
during run)
04
deceleration (valid during
run)
05
stop(valid during run)
the
motor;
six
:
Controlled
(invalid
:
Controlled
:
DC
braking
to
16
Run
Default
mode
edit
02
×
02
×
60.0
×
6.00
04
×
High level
access
mode
×
×
×