6-6-3. Interlocked LOSSNAY settings
The ON/OFF status of the LOSSNAY or LOSSNAY with heater/humidifier can be interlocked with the operation
of indoor units.
Note
• The ON/OFF status of the indoor units are not interlocked with the ON/OFF status of the LOSSNAY unit.
Procedures
1. Click [Unit Settings] > [Interlocked LOSSNAY] to access the interlocked LOSSNAY settings screen.
Interlocked LOSSNAY
registration
Click to display the screen
for registering the LOSSNAY
unit to be interlocked.
2. Click the icon in "Interlocked LOSSNAY registration" (
3. Select the address number of the LOSSNAY to be interlocked, and click [OK].
4. Click the icon in "Interlocked indoor unit registration" (
5. Select the address number of the indoor units with whose operations are to be interlocked, and click [OK].
Each LOSSNAY can be interlocked with up to 16 indoor units.
6. Click [Save] to save the settings.
WT07442X02
Save
Click to save the settings.
) to display the unit address selection screen.
) to display the unit address selection screen.
77
Interlocked indoor unit
registration
Click to display the screen
for registering the indoor
units with whose operations
are to be interlocked.
Back
Click to display the previous
settings without making any
changes.