1. Specification
HP
Model Name
Capacity
Cooling
Heating
Input
Cooling
Heating
Casing Color
Heat Exchanger
Compressor
Type
Maker
Piston Displacement
Number of Revolution
Motor Output x Number
Starting Method
Oil Type
Oil Charge
Fan
Type
Motor Output x Number
Air Flow Rate(High)
Drive
Discharge
Pipe Connctions
Liquid Pipes
Gas Pipes
Dimensions (W*H*D)
Net Weight
Transmission Cable
Refigerant
Refigerant name
Control
Power Supply
Notes:
1. Capacities are based on the following conditions:
Cooling * Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
* Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
* Interconnecting Piping Length 7.5m
* Level Difference of Zero
Heating * Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
* Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
* Interconnecting Piping Length 7.5m
* Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. L.E.V.:Linear Expansion Valve
W
kcal/h
Btu/h
W
kcal/h
Btu/h
kW
kW
cm
2
/rev
r.p.m
W
CC
W
cmm
cfm
mm(inch)
mm(inch)
mm
inch
kg
lbs
mm
2
Ø / V / Hz
Specification
Heat Pump(50Hz)
10
ARUN1008F20
28,000
24,100
95,500
31,500
27,100
107,500
7.18
7.69
WARM GRAY
Louver Fin
Rotary
Matsushita
42.4*2
3450*2
4500*2
Direct on Line
FV50S(PVE)
1300*2
Siroco Fan
840*2
170
6,004
Inverter
Front
Ø9.52(3/8)
Ø22.2(7/8)
1400*1790*650
55.1*70.5*25.6
350
771.6
CVV-SB 1.25X2C
R410A
L.E.V
3 / 380 ~ 415 / 50
Conversion Formula
Kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
Service Manual 81
3
/min x 35.3

Hide quick links: