Installation of indoor unit
Checking for gas leakage
1)Check for leakage of gas after air purging
2)See the sections on air purges and gas leak checks in the installation
manual for the outdoor unit
Attaching the connection pipe
• Attach the pipe after checking for gas leakage, described above.
1)Cut the insulated portion of the on-site piping, matching it up with the connecting portion.
2)Secure the slit on the refrigerant piping side with the butt joint on the auxiliary piping using the tape, making
sure there are no gaps
3)Wrap the slit and butt joint with the included insulation sheet, making sure there are no gaps
CAUTION
1.
Insulate the joint of the pipes securely.
Incomplete insulation may lead to water leakage.
2.
Push the pipe inside so it does not place undue force on the front grille
Connecting the drain hose
Insert the supplied C drain hose into the
socket of the drain pan.
Fully insert the drain hose until it
adheres to a seat of the socket
INSTALATION INSTRUCTIONS
Check for leakage here
Apply soapy water
and ch-
eck carefully for
leaking gas.
wipe soapy water
off after
the check is
complete.