Commissioning, inspection, maintenance

Checking the condensate drain and cleaning the trap

C
A
B
Fig. 26

Installing the burner

A 4x
F
E
D
Fig. 27
1. Mount burner and secure with 4 screws
2. Insert the new gasket and tighten the fitting on gas
supply pipe
.
B
34
B
C
.
A
1. Release hook and remove trap
piece
.
B
Pull trap
upwards away from the drain connec-
A
tion.
2. Remove supply hose
3. Clean trap
.
A
4. Insert trap
A
with sealing piece
Refit trap
to the drain connection.
A
5. Refit supply hose
.
C
6. Fill trap
with water. For this, pour approx. 0.3 l
A
of water into the combustion chamber.
7. Check that condensate can drain freely and that
the connections are tight.
A
with sealing
C
from trap
A
.
B
.